EFFICIENT SERVICEABILITY.

Our angle isolation valves feature an optimized body chamber for maximum flow, and a "Quick-Change" packing gland allows easy replacement of the asbestos-free packing without loss of refrigerant. The backseating stem and seat design provides minimal pressure drop. Rotolock and sweat configurations are customized to specific applications with special brass and steel configurations available.

Angle Isolation Valves Masthead
back ↵

Style: Brass – Solder to Rotolock

Mueller Industries Photo

Quality & Technical Information

  • Design Pressure (DP) / Maximum abnormal pressure (MAP): 700 psig, 48 bar
  • Continuous operating temperature (COT): -40°F/300°F, -40°C/149°C
  • UL/cUL Recognized, Conforms to EU Pressure Equipment Directive and UK Pressure Equipment Regulation
  • 100% tested
  • Asbestos-free packing material
  • Quick-change packing gland allows easy replacement without refrigerant loss
  • Solid brass construction for maximum protection in all environmental conditions
  • Backseating design

Uses

  • Refrigeration
  • Air Conditioning
Mueller Industries Graphic

Specifications & Technical Drawings

  • Brass Angle Isolation Valve, Solder to Rotolock Style – Dimensions – English / Metric

    PDF

  • Brass Angle Isolation Valve, Solder to Rotolock Style – Dimensions – Chinese

    PDF

  • Brass Angle Isolation Valve, Solder to Rotolock Style – Dimensions – Spanish

    PDF

  • Installation Instructions